Items
|
Description
|
FSL100 Flame detector types
|
FSL100-UV, FSL100-UVIR and FSL100-IR3; Choice of red or white housings
|
Range
|
110 ft /35 m (IR3), 25 m/80 ft (UV, UV/IR) alarming within 10 seconds to a 1 ft2(0.1 m2) n-heptane fire
|
Cone of vision
|
90˚minimum horizontal and vertical
|
Power
|
10-28 VDC (12-24 VDC nominal)
|
Local LEDs
|
Continuous green: normal operation
Continuous yellow: fault
Flashing yellow: Fault and guide to repeat self-test after a self-test failure
Continuous red: alarm
|
Current output
|
Standard available 4–20mA (stepped, sinking, non-isolated)
|
Relay output
|
De-energized during normal operation, no alarm, SPDT, 30 VDC – 2 A, 60 W max. Energized during normal operation, no fault, SPDT, 30 VDC – 2 A, 60 W max.
|
Cable gland & terminals
|
Cable entry M20 clearance. Supplied with gland suitable for cable diameter from 0.2” (5.5mm) to 0.5”(13mm). Terminals
suitable for 0.5mm2 (20AWG) to 1.5mm2 (15AWG) wire
|
Start up times
|
<10 sec
|
Alarm response time
|
8 to 30 sec
|
Alarm output settings
|
Selectable LEDs and relays latching/non-latching; factory setting: latching
|
Automatic & manual Self-Test
|
Automatic Sensor Test (built in Self-Test) and manual Self-Test
|
Operating current normal
|
25mA at 24 VDC
|
Current in alarm, at 24 VDC
|
±75mA at 24 VDC
|
Connections to
|
Fire control panels using end of line (EOL) and alarm resistors (current increase), Devices that operate via relay switched outputs, PLCs with 4–20mA inputs
|
End of line and alarm resistor
|
To be adjusted to the fire control panel; free terminals are dedicated to the resistors
|
Housing
|
Glass Reinforced Polyester (GRP), Non-incentive. UV resistant, Self-Extinguishing V–0 (UL-94)
|
Swivel mount
|
PA66, UV resistant; Stainless Steel fixings; 280 g (0.62 lb)
|
Pressure compensating element
|
PCE (Pressure Compensating Element) avoids moisture build-up in the detector housing due to changes in ambient air-pressure
|
Ingress protection
|
P65
|
Temperature, operating
|
–40℉ to +158℉ (–40℃ to +70℃)
|
Temperature, ambient ATEX and FM class 3611
|
–13℉ to +158℉ (–25℃ to +70℃)
|